Creative combining for much comfort
The CD+ range is a series of warm water boilers that contains five types of increasing capacities. These direct fired boilers are very innovative within the warm water supply. The fully stainless steel boiler is suitable for warm tap water.
Many combination options
By combining the CD+ boiler with the patented water tank we offer unique solutions. Thanks to the many boiler-tank combinations the system can be precisely aligned with the warm water need. For example, a high peak load with a short recovery period can be selected for showers in sport clubs, or for long term continuous availability of warm water at care institutes.
Patented tanks
The CD+ boiler is always installed in combination with our patented tanks. These tanks are made from high-quality stainless steel and covered with a good insulation to limit the downtime losses. The tanks are equipped with a patented injection system. With this system it is possible to continuously tap warm water from the tank with the tap water boiler in the condensing area. A high efficiency is the result, while the temperature of the flowing water remains constant.
The CD+ boiler is supplied exclusive pump, for an optimal operation of our boilers we supply pumps selected by us.
Features CD+ boiler
✓ Large continuous tap capacity
✓ Very quick heating time of a full storage tank
✓ Recovery time less than 10 minutes
✓Simple technique
✓ Fully stainless steel, so suitable for tap water
✓ Compact construction
✓ No boiler thermostat, so no waiting time for starting the boiler
✓ The device always condensates, so efficiency higher than 100% during the tapping of tap water up to 60°C
✓ Adjustable tap water temperature from 35º to 75°C
✓ Pomp switch for frost protection
✓ Link with GBS and company report possible
Popular specifications
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
|
---|---|---|---|---|---|---|
Dimensions (h x w x d) | mm | 842 x 476 x 486 | 898 x 476 x 677 | |||
Weight empty | kg | 68 | 73 | 78 | 87 | 96 |
Flue-gas/air parallel | mm | 80-80 | 100-100 | 100-100 | 130-130 | 130-130 |
Load (ow) (G25) | kW | 14,6 – 74,3 | 17,2 – 92,2 | 26,0 – 111 | 34,0 – 138 | 45,0 – 166 |
Efficiency 50/30 °C | % | 107,9 | 107,9 | 108,2 | 107,9 | 107,8 |
Available flue-gas/air duct resistance* | Pa | 200 | ||||
*Maximum allowed external joint resistance flue-gas and air duct on full load |
General
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
|
---|---|---|---|---|---|---|
Dimensions (h x w x d) |
mm | 842 x 476 x 486 | 898 x 476 x 677 | |||
Water volume | Liter | 5,0 | 6,5 | 8,3 | 10,4 | 12,9 |
Weight empty | kg | 68 | 73 | 78 | 87 | 96 |
Cold and warm water connection | inch | 1½ | 2 | 2 | 2 | 2 |
Connection size gas | inch | R ¾ | R ¾ | R ¾ | R 1 | R 1 |
Flue-gas/air concentric | mm | 80/ 125 |
100/ 150 |
100/ 150 |
100/ 150 |
100/ 150 |
Flue-gas/air parallel | mm | 80-80 | 100-100 | 100-100 | 130-130 | 130-130 |
Capacity
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
|
---|---|---|---|---|---|---|
Load (ow) (G25) | kW | 14,6 – 74,3 | 17,2 – 92,2 | 26,0 – 111 | 34,0 – 138 | 45,0 – 166 |
Load (bw) (G25) | kW | 16,2 – 82,5 | 19,1 – 102 | 28,9 – 123 | 37,8 – 153 | 50,0 – 184 |
Load (bw) (G31) | kW | 15,9 – 80,8 | 18,7 – 100 | 28,3 – 121 | 37,0 – 150 | 48,9 – 180 |
Load (bw) (G30) | kW | 15,8 – 80,2 | 18,6 – 99,7 | 34,7 – 120 | 36,8 – 150 | 48,8 – 180 |
Efficiency 50/30ºC | % | 107,9 | 107,9 | 108,2 | 107,9 | 107,8 |
Gas consumption
G30*50 (43 – 57)
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
||
---|---|---|---|---|---|---|---|
Natural gas G25 | m³st/u | 1,80 – 9,14 | 2,12 – 11,4 | 3,20 – 13,7 | 4,18 – 17,0 | 5,54 – 20,4 | |
Propane G31* | m³st/u | 0,60 – 3,04 | 0,70 – 3,77 | 1,06 – 4,54 | 1,39 – 5,65 | 1,84 – 6,79 | |
Butane G30 (B/P)* | m³st/u | 0,45 – 2,29 | 0,53 – 2,85 | 0,99 – 3,44 | 1,05 – 4,28 | 1,40 – 5,15 | |
Gas connection pressure nom. (min – max) |
G25 | mbar | 25 (20 – 30) | ||||
G31* | 30 (25 – 35) / 37 (25-45) | ||||||
*With the use of propane G31 or butane G30 the maximum ventilator speed must be reduced (parameter P4BD) |
Emission
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
||
---|---|---|---|---|---|---|---|
CO2 Flue-gas min-max* |
G25 | % | 8,7 – 9,0 | 8,7 – 9,0 | 8,7 – 9,0 | 8,7 – 9,0 | 8,7 – 9,0 |
G31 | % | 9,3 – 10,3 | 9,3 – 10,3 | 9,3 – 10,3 | 9,3 – 10,4 | 9,3 – 10,5 | |
G30 | % | 9,3 – 10,4 | 9,3 – 10,4 | 9,3 – 10,4 | 9,3 – 10,5 | 9,3 – 10,6 | |
Noise capacity level (EN 15036-1:2006) | dB(A) | 67 | 65 | 62 | 66 | 69 | |
NOx classification [EN483/EN15420] | – | 6 | |||||
Temp. flue-gas at combustion air temperature 20°C | °C | ~ 85-95 | |||||
Max. flue-gas volume | g/s | 38,6 | 47,9 | 57,7 | 71,7 | 86,2 | |
Resistance flue-gas/air duct** | Pa | 200 | |||||
* CO2 of the device measured/set without installed boiler door. ** Maximum allowed joint flue-gas and air duct resistance measured when the device is burning at full load. |
Installation
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
|
---|---|---|---|---|---|---|
Maximum water temperature | °C | 75 | ||||
System pressure min-max | bar | 1,0-8,0 | ||||
Overflow pressure max | 10 | |||||
Available external resistance for the installation at ΔT= 17 K | mWK | 5,8 | 4,7 | 4,1 | 6,0 | 5,5 |
Electric
Device type: | CD+ 80 |
CD+ 100 |
CD+ 120 |
CD+ 150 |
CD+ 180 |
|
---|---|---|---|---|---|---|
Included electrical power | W | 170 | 170 | 190 | 250 | 250 |
Electrical supply | V / Hz | 230 / 50 | ||||
IP classification | IPX4D |
Other
CE product ID number | CE 0063 BP3254 |
Gas category | II2L3B/P |
Device category | B23; B23P; C13X, C23X, C33X, C43X, C53X, C63X, C83X |
Football Club Losser, NL
Hot water: CD 80 combined with a 300 liter storage tank
Sports Centre Papendal, NL
Hot water: 2 pieces of CD 100 combined with a 450 liter storage tank
Meulenbelt in Almelo, NL
Central Heating: 3 pieces of Senator+ 400
Hot water: 2 pieces of CD+ 80 combined with a 450 liter storage tank
NH Hotel in Amsterdam, NL
Hot water: 4 pieces of CD 180 combined with 2 pieces of 450 liter storage tanks
Care facility Het Roessingh in Enschede, NL
Hot water: 2 pieces of CD 100 combined with 2 pieces of 300 liter storage tank