Modular customized system for any boiler room
The incorporated cascade regulator makes the CB CH the ideal boiler for cascade systems up to twelve boilers. Simple looping and straight-forward connections make the installation easy. With the supplied cascade rack, a capacity of more than two megawatts can be installed in the most inaccessible areas. The system is equipped with adjustable legs and does not have to be anchored to the wall.
Features cascade
✓ Complete cascade set including assembly manual
✓ Water-side supply and return pipe
✓ Open distributor
✓ Gas-side distributor
✓ Open distributor sensor
✓ Connection set for the individual boilers
✓ Common flue system available
Popular specifications
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
Dimensions (h x b x d) |
mm |
845 x 440 x 530 |
Weight empty |
kg |
77 |
79 |
83 |
86 |
Flue connection concentric pipe |
mm |
100/150 |
100/150 |
100/150 |
N/A |
Flue connection twin pipe |
mm |
100 |
100 |
100 |
150 |
Nominal input (Net) |
kW |
15,4 – 81,7 |
18,6 – 97,3 |
23,6 – 119,4 |
35,0 – 145,3 |
Nominal input 80/60°C |
kW |
14,9 – 79,1 |
18,0 – 94,2 |
22,9 – 115,7 |
33,9 – 140,9 |
Efficiency (input 30%, return 30°C) |
% |
108,2% |
108,4% |
108,4% |
108,6% |
Nitrogen Dioxide Emission (NOx) |
mg/kWh |
23,1 |
21,3 |
23,9 |
20,1 |
General
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
Dimensions (h x w x d) |
mm |
845 x 440 x 530 |
Water content (estimated) |
liter |
5,0 |
6,5 |
8,3 |
10,4 |
Weight (empty) |
kg |
77 |
79 |
83 |
86 |
Supply /return connection (boiler) |
inch |
1” |
1” |
1” |
1 ¼” |
Gas connection |
inch |
¾” |
¾” |
¾” |
1” |
Flue connection twin pipe |
mm |
100 |
100 |
100 |
150 |
Flue connection concentric pipe |
mm |
100/150 |
100/150 |
100/150 |
N.A. |
Gas appliance type |
– |
B23(P), C13, C33, C43, C53, C63, C83, C93 |
Heating
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
Nominal input net G20 |
kW |
15,4 – 81,7 |
18,6 – 97,3 |
23,6 – 119,4 |
35,0 – 145,3 |
Nominal output G20 (80-60) |
kW |
14,9 – 79,1 |
18,0 – 94,2 |
22,9 – 115,7 |
33,9 – 140,9 |
Nominal output G20 (50-30) |
kW |
16,0 – 85,1 |
19,5 – 101,8 |
24,7 – 124,7 |
36,4 – 151,0 |
Nominal output G20 (37-30) |
kW |
16,6 – 88,4 |
20,2 – 105,5 |
25,6 – 129,7 |
38,0 – 157,8 |
Turndown ratio |
1:x |
5 |
5 |
5 |
4 |
Efficiency (input 30%, return 30°C) |
% |
108,2% |
108,4% |
108,4% |
108,6% |
Seasonal efficiency (Part L) |
% |
95,6% |
95,7% |
95,7% |
95,8% |
Seasonal space heating energy efficiency (ɳs) |
% |
92,4% |
92,6% |
92,7% |
92,9% |
Gas consumption
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
G20 |
m3/h |
1,6 – 8,5 |
1,9 – 10,2 |
2,5 – 12,5 |
3,7 – 15,3 |
G31 |
m3/h |
0,6 – 3,2 |
0,8 – 3,9 |
1,0 – 4,8 |
1,6 – 15,7 |
Gas supply pressure nominal |
G20 |
mbar |
20 |
G31 |
mbar |
37 |
Emission
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
NOx class |
– |
6 |
Nitrogen Dioxide Emission (NOx) 1 |
mg/kWh |
23,1 |
21,3 |
23,9 |
20,1 |
Flue gas temperature at combustion air temperature of 20 °C |
°C |
60 – 90 |
Available pressure for the flue system2 |
Pa |
200 |
Noise level |
dB(A) |
65,8 |
68,0 |
67,8 |
73,0 |
Installation
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
Maximum supply temperature |
°C |
90 |
Resistance water heater ΔT = 20 °C |
mWc |
4,0 |
3,4 |
3,8 |
3,6 |
Resistance water heater ΔT = 25 °C |
mWc |
2,8 |
2,3 |
2,5 |
2,4 |
Pressure boiler |
bar |
1,0 – 6,0 |
Electric
Boiler model |
|
CB-85-CH |
CB-105-CH |
CB-125-CH |
CB-155-CH |
Maximum power consumption |
W |
190 |
280 |
280 |
280 |
Power supply |
V/Hz |
230 / 50 |
Protection class |
– |
IPX4D |